Máy phân tích nguồn 1&3 pha PA3000

Hãng sản xuất

Tektronix

Model: PA3000

Giá: Liên hệ

Có sẵn: call

Gọi để có giá tốt

024 62.510. 510
Mr. Lịch 0913. 381. 016
Mr. Tuân 0977. 708. 790

Specifications

All specifications are guaranteed unless noted otherwise. All specifications apply to all models unless noted otherwise. Specifications are subject to change without notice.

For detailed information on the PA3000 Power Analyzer product specifications refer to the Model PA3000 Power Analyzer Instrument Specifications document, Tektronix part number 077-1252-00 downloadable fromwww.tek.com/manual/downloads.

Current accuracy
Accuracy Arms
(45 Hz to 850 Hz)

1 A shunt
±0.04% reading ±0.04% range
30 A shunt
±0.04% reading ±0.04% range
External shunt
±0.1% reading ±0.04% range
Accuracy Arms, typical
(10 Hz to 45 Hz, 850 Hz to 1 MHz)

1 A shunt
±(0.05 + 2×10-5 × f)% reading ±0.05% range ±40 μA
30 A shunt
±(0.05 + 2×10-5 × f)% reading ±0.05% range ±4 mA
External shunt
±(0.1 + 2×10-5 × f)% reading ±0.05% range ±1.1 mV
Accuracy Adc
1 A shunt
±0.05% reading ±0.1% range ±100 μA
30 A shunt
±0.05% reading ±0.1% range ± 10mA
External A shunt
±0.1% reading ±0.1% range ±1.1 mV
Ranges
(peak)

1 A shunt
12.5 mA, 25 mA, 50 mA, 125 mA, 250 mA, 500 mA, 1.25 A, 2.5 A, 5 A
30 A shunt
500 mA, 1 A, 2 A, 5 A, 10 A, 20 A, 50 A, 100 A, 200 A
External A shunt
50 mV, 100 mV, 200 mV, 500 mV, 1 V, 2 V, 5 V, 10 V, 20 V
Voltage accuracy
Accuracy Vrms (45 Hz to 850 Hz)
±0.04% reading ±0.04% range
Accuracy Vrms (10 Hz to 45 Hz, 850 Hz to 1 MHz), typical
±(0.05 + 1×10-5 × f)% reading ±0.05% range ±20 mV
Accuracy Vdc
±0.05% reading ±0.1% Range ±50 mV
Ranges (peak)
5 V, 10 V, 20 V, 50 V, 100 V, 200 V, 500 V, 1000 V, 2000 V
Supplemental characteristics

The following specifications are supplemental characteristics that provide additional information about instrument functions and performance. These characteristics are non-warranted specifications; they describe the typical performance of the PA3000.

For detailed information on the PA3000 Power Analyzer product specifications refer to the Model PA3000 Power Analyzer Instrument Specifications document, Tektronix part number 077-1252-00 downloadable fromwww.tek.com/manual/downloads.

Hours accuracy
±0.0125%
Watts accuracy (45 Hz to 850 Hz)
±(Vrmsacc × Arms) ±(Armsacc × Vrms)
Watt hour accuracy
±(Wattacc + Houracc)
VA accuracy (45 Hz to 850 Hz)
±(Vrmsacc × Arms) ±(Armsacc × Vrms)
PF accuracy
Wacc / VA
Frequency accuracy
0.1 Hz to 10 Hz
0.1% of reading
10 Hz to 1 MHz
0.5% of reading
Analog inputs
Ranges
10 Vdc range: ±1 V to ±10 VVdcrange: ±0.1 V to ±1 V
Accuracy
±0.2% of reading ±0.2% of range ±0.005 V
Sample rate
1000 samples per second
Communications
IEEE-488 (Option)
IEEE Std 488.1 compliant
RS-232 
Baud rates from 9600 bps, 19200 bps (default), and 38400 bps

8 bit, No parity, 1 stop bit, hardware flow control

9 pin male D-type connector

Ethernet
IEEE 802.3 compatible, 10Base-T

RJ-45 connector with Link and Activity indicators

TCP/IP connection on port 5025

USB device
USB 2.0 compatible, Full speed (12 Mb/sec)
General specifications
EMC
Conforms to European Union EMC directive
Safety
Conforms to European Union Low Voltage directive
Temperature
Operating
0 °C to 40 °C (32 °F to 104 °F), 70% relative humidity up to 31 °C (87.8 °F)
Storage
-25 °C to 65 °C (-13 °F to 149 °F)
Altitude
Up to 2000 m (6562 ft) above sea level
Warm up time
One hour
Calibration period
One year
Power supply
100 V to 240 VAC, 50 Hz or 60 Hz, 120 VA maximum
Transducer power supply
±15 V, Maximum current 250 mA per analog card
Dielectric strength
Mains supply inlet (Live + Neutral to earth): 1.5 kVAC

Voltage measurement inputs : 2 kVpkto earth

Current measurement inputs : 2 kVpkto earth

Dimensions
With handle and feet
14.6 cm high × 45 cm wide × 33.5 cm deep (5.75 in × 17.75 in × 13.2 in)
Without handle and feet
13.2 cm high × 42 cm wide × 33.5 cm deep (5.2 in × 16.5 in × 13.2 in)
Weight
9.5 kg (20.9 lb) – 4 channel instrument with GPIB option installed
Warranty
Three years